Modell: KH-400GF
Technical Specification | |||||
1. Specification of Genset | |||||
Genset Model | KH-40 | ||||
Prime Power(KW) | 400 | ||||
Rated Voltage (V) | 400 | ||||
Rated Current (A) | 720 | ||||
Rated Frequency(Hz) | 50 | ||||
Power Factor(COSφ) | 0.8 | ||||
Rated Speed | 1500rpm | ||||
Dimensions (L×W×H)--Silent Type (mm) | 4700x2100x2450 | ||||
Genset Weight--Silent Type (kg) | 6000 | ||||
2. Specification of Engine | |||||
Engine Brand | Cummins | ||||
Engine Model | QSZ13-G3 | ||||
Number of Cylinders | 6 | ||||
Cylinder Arrangement | Vertical in-line | ||||
Cycle | Four stroke | ||||
Air intake System | Turbocharged &charge air cooled | ||||
Fuel System | XPI | ||||
Bore×Stroke (mm) | 114x 145 | ||||
Displacement (L) | 13 | ||||
Compression Ratio | 17.0:1 | ||||
Governor Type | Electronic | ||||
Cooling System | Water Cooled | ||||
Total lubrication System Capacity (L) | 40.6 | ||||
Fuel Consumption at 100% Load(g/kwh) | 202 | ||||
Starting Method | DC24V electrical starting | ||||
3. Specification of Alternator | |||||
Alternator Brand | Stamford | ||||
Alternator Model | HCI544C | ||||
Excitation | Brushless ,Self-exciting, AVR automatic voltage regulating,100% Copper winding wire | ||||
Number of Phase | 3 | ||||
Connecting Type | 3 Phase and 4 Wires | ||||
Number of Bearing | 1 | ||||
Power Factor | 0.8 | ||||
Protection Grade | IP23 | ||||
Altitude | ≤1000m | ||||
Insulation Class, Temperature Rise | H | ||||
Telephone Influence Factor (TIF) | ≤50 | ||||
THF | ≤2% | ||||
Voltage Regulation, Steady State | ≤±1% | ||||
Transient State Voltage | ≤-15%~+20% | ||||
4.Specification of Control Module | |||||
The features of Control Module : | |||||
The control panel is the one with automatic start function, and the controller uses LCD display, optional Chinese and English display interface with operation easy and reliable. It can be widely used in all types of generator automatic control system for compact structure, advanced circuits, simple connections and high reliability. | |||||
The protection functions of Control Module : | |||||
Protection functions: It will give alarm signals when the output parameters exceed the items stated below and at the same time the generator set should be stopped or delay stopping and fails to self start; Over voltage and low voltage,over frequency,over speed,low oil pressure,high temperature, low water level and over load. |