Zahlungsart: | L/C,D/A,D/P,T/T,Western Union,MoneyGram |
---|---|
Minimum der Bestellmenge: | 1 Set/Sets |
Lieferzeit: | 10 Tage |
Modell: KH-600GF
1. Specification of genset | |
Gensets Model | KH-600GF |
Prime Power(KW) | 600 |
Standby Power(KW) | 660 |
Rated Voltage(V) | 230/400 |
Rated Current(A) | 1080 |
Rated Frequency(HZ) | 50 |
Rated Speed (rpm) | 1500 |
Power Factor(COS) | 0.8(lagging) |
Prime Power(PRP):Prime power is available for an unlimited number of annual hours in variable load application,in accordance with GB/T2820-97;A 10% overload capability is available for a period of 1 hour within a 12-hour of operation. | |
Standby Power Rating(ESP):The standby power rating is applicable for supplying emergency power for the duration of a utility power interruption.No overload,utility parallel or negotiated outage operation capability is available at this rating. | |
2. Specification of diesel engine | |
Engine brand | Shangchai |
Engine model | SC33W990D2 |
Number of Cylinders | 6 |
Cylinder arrangement | In line |
Cycle | Four stroke |
Fuel System | Direct Injection |
Bore×Stroke (mm×mm) | 180x215 |
Displacement (Liter) | 32.8 |
Speed Governor | Electrical |
Cooling System | Water-cooled |
Fuel Consumption at 100% Load (g/kw.h) | 215 |
Starting Method | DC24V electrical starting |
3. Specification of alternator | |
Alternator brand | Kaihua |
Alternator model | KH404B |
Number of Phase | 3 |
Connecting Type | 3 Phase and 4 Wires |
Number of Bearing | 1 |
Protection Grade | IP21 |
Altitude | ≤1000m |
Exciter Type | Brushless ,Self-exciting, AVR automatic voltage regulating,100% Copper winding wire |
Insulation Class | H |
Telephone Influence Factor (TIF) | ≤50 |
THF | ≤2% |
Voltage Regulation, Steady State | ≤±1% |
Transient State Voltage | ≤-15%~+20% |
Produktgruppe : Chinesische Marke Diesel-Generatoren > Shangchai Diesel-Generatoren