Zahlungsart: | L/C,D/A,D/P,T/T |
---|---|
Minimum der Bestellmenge: | 1 Set/Sets |
Lieferzeit: | 15 Tage |
Modell: KH-24GF
1. Specification of genset | ||||||||
Gensets Model | KH-24GF | |||||||
Prime Power(KW) | 24 | |||||||
Standby Power(KW) | 30 | |||||||
Rated Voltage(V) | 380 | |||||||
Rated Frequency(HZ) | 50 | |||||||
Rated Speed (rpm) | 1500 | |||||||
Power Factor(COS) | 0.8(lagging) | |||||||
Prime Power(PRP):Prime power is available for an unlimited number of annual hours in variable load application,in accordance with GB/T2820-97;A 10% overload capability is available for a period of 1 hour within a 12-hour of operation. | ||||||||
Standby Power Rating(ESP):The standby power rating is applicable for supplying emergency power for the duration of a utility power interruption.No overload,utility parallel or negotiated outage operation capability is available at this rating. | ||||||||
2. Specification of diesel engine | ||||||||
Engine brand | Deutz | |||||||
Engine model | D226B-3D | |||||||
Number of Cylinders | 3 | |||||||
Cylinder arrangement | Vertical in-line | |||||||
Cycle | Four stroke | |||||||
Aspiration | Natural | |||||||
Bore×Stroke (mm×mm) | 105x120 | |||||||
Displacement (Liter) | 3.12 | |||||||
Compression Ratio | 16.5:1 | |||||||
Speed Governor | Mechanical | |||||||
Cooling System | Water-cooled | |||||||
Total lubrication system capacity (L) | 7.25 | |||||||
Fuel Consumption at 100% Load (L/h) | 6.5 | |||||||
Starting Method | DC24V electrical starting | |||||||
3. Specification of alternator | ||||||||
Alternator brand | KAIJIELI | |||||||
Orgin | SuZhou | |||||||
Alternator model | TWGII184H | |||||||
Number of Phase | 3 | |||||||
Connecting Type | 3 Phase and 4 Wires | |||||||
Number of Bearing | 1 | |||||||
Protection Grade | IP21 | |||||||
Altitude | ≤1000m | |||||||
Exciter Type | Brushless ,Self-exciting, AVR automatic voltage regulating,100% Copper winding wire | |||||||
Insulation Class | H | |||||||
Telephone Influence Factor (TIF) | ≤50 | |||||||
THF | ≤2% | |||||||
Voltage Regulation, Steady State | ≤±1% | |||||||
Transient State Voltage | ≤-15%~+20% | |||||||
4. Specification of control Panel | ||||||||
The control panel is AMF control panel, with the display of voltage,current, frequency, water temperature, oil pressure. The genset with low oil pressure,high water temperature,over speed,over load protection function. |
Produktgruppe : DEUTZ-Diesel-Generatoren